Lakewood Tenants Association

655 John Muir Drive,  #411, San Francisco, CA    lakewoodtenants@hotmail.com     (415) 334-0465

 

 

                                                                                                January 24, 2008

 

Haley Gonzaba, Manager                                                       

Lakewood Apartments                                                            

515 John Muir Drive

San Francisco, California 94132-1020

 

1.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, March 27, 2004

2.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, August 18, 2004

3.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, February 8, 2005

4.) Letter, Amy Sexton, manager, to Mona Cereghino, February 16, 2005

5.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, March 7, 2005

6.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, June 8, 2005

7.) Letter, Lakewood Tenant Association to Amy Sexton, manager, Lakewood Apartments, September 30, 2005

8.) Letter, Lakewood Tenant Association to Amy Sexton, manager, January 26, 2006

 

Re: Door Survey

 

Dear Ms. Gonzaba:

 

We have performed a partial survey of the exterior doors that secure the property, as we have from time to time in the past. The findings of the survey are identification of a number of doors that fail to perform their security function; the results are summarized on the attached form. The survey included an evaluation of only those doors for which a written entry was made on the form. Each door was inspected to determine (a) if there were any loose or missing fasteners securing the latch, latch strike, door closer or hinges; (b) whether the latch operated properly (including whether it was well enough lubricated so as to not defeat the self-closing action of the door); (c) Whether there was any interference between the door and the door-jamb that retards door closure; (d) whether the door closer provided adequate closing force throughout the full swing of the door and (e) any other miscellaneous problems that may interfere with the security of the doors. While many doors operated properly there were still a significant number of doors that fail to maintain the security of the property. For example, one door was found unlocked, one with its latch defeated with tape (see attached photos), two doors that could be pushed open even though closed fully, and there were several doors bent such that they had to be slammed to cause the latch to drop into the strike.

 

A longstanding problem is that two doors (A building, 2nd floor, near parking space 225 and D Building, 1st floor, near parking space 372) have had the electronic latch removed to convert those doors to emergency exits from the garages into the building thus allowing intruders potential unrestricted access at those locations. Jeff Blankenship, your maintenance manager, told us during our inspection that Lakewood has a letter or letters that establish that the Department of Building Inspection and the Fire Department have inspected those doors and have approved the conversion to emergency exits. That inspection by the city was no doubt performed at our request years ago and yet we do not recall any communication ever being made from either city department to us to disclose or explain their determinations and Wednesday was the first time we have heard of any such letter being provided to Lakewood. Therefore, we request from you a copy of the letter or letters described to us today by Jeff for our evaluation.

 

We also note that Jeff Blankenship told us during our inspection that Senior Building Inspector Alan Davison had stated to him in the past that the proper way to inspect a door for its capability to self close is to open the door fully and walk through. The San Francisco Housing Code makes no such distinction. Section 705 provides the purpose of the standards to be "...to provide minimum standards to ensure [our emphasis] the security of existing hotels, motels and apartment houses ... particularly regarding point of entry into buildings." Section 705(b)(1)(i) requires exterior doors to be "self-closing" and there is no qualification or exception to that standard. Furthermore, there is no explicit definition in sections 400 or 401 of the term "self-closing" so we believe that, consistent with the obvious purpose of the standards as expressed in section 705, the doors should close themselves no matter from what position of rest the door is released from. Indeed, most of the doors at this property do close even when released from just a couple inches. A perfect example of a door that would pass the standard supposedly expressed by Mr. Davison but which we believe fails to meet the intent of the Housing Code standards is the door on the first floor of the D building in a stairwell (record # 48 on the attached form). The door can sit open by about a foot and yet, if it is opened fully, the door will self close. (The reason appears to be fasteners coming loose in the attachment of the door closer arm to the door frame.) You may note that we indicate on the attached survey form a number of instances where a door was found to "rest." That is shorthand to mean that the door was found capable of resting against the latch and thus failing to self close. We consider that to be a clear violation of explicit Housing/Building codes regardless of what the building inspector may have stated to others. Even if we are incorrect in that interpretation, we still believe that the landlord has a duty to maintain the property in a condition that provides tenants a reasonable expectation that criminals cannot enter through an exterior door unheeded under the implied warrantee of habitability doctrine, not to mention plain common sense. Therefore, we stand behind our inspection methodology.

 

As a final note, previous managers, at our suggestion, have caused the doors to have numbers applied at or adjacent to the door frames to facilitate tracking by your maintenance department and security guards. Different numbering systems have been applied to the doors at different times. At this point in time, many of the door numbers have been painted over or are otherwise missing. Commitments were made in the past to periodically monitor the security of the doors against a list. We do not see how those commitments could be kept without maintaining the numbering system. The results of our inspection suggest to us that, once again, inspection and maintenance of the doors that should secure this property from criminals is in need of improvement.

 

                                                                                                Sincerely,

 

 

 

                                                                                                Mona Cereghino, President

 

 

 

                                                                                                Ross Wilkinson, Vice-president


           

 

Exterior door, E Building garage near parking space # 724, latch and strike vandalized with tape defeating security (note also plugged storm drain)